Cabling

Fiber patch cable color codes: what yellow, aqua, orange and violet mean

Yellow, aqua, orange, violet, a blue or green connector: what fiber patch cable colors mean under TIA-598, and why you still read the print on the jacket.

4 min readBy Yvan Watchman

Color is a convention, not proof. Yellow: jacket: single-mode. Blue: connector: UPC. Green: connector: APC. Aqua: OM3 and OM4 (TIA-598). Erika violet: OM4, common in Europe. Multimode to single-mode costs around 17 to 20 dB (FOA). Read the print on the jacket.

You're standing at a patch panel with a box of patch cords in four colors and you need to grab the right one. Or you've inherited a rack where someone plugged a yellow cable into a multimode port. This article gives you a table of what jacket and connector colors mean, where manufacturers deviate, and the one rule that always saves you: read the print.

Jacket colors under TIA-598

Fiber cable colors come from TIA-598. It's a US standard, but most manufacturers follow it, in Europe too.

Fiber typeJacketConnector
OS1 / OS1a / OS2 (single-mode)yellowblue (UPC), green (APC)
OM1 (62.5/125)orangebeige
OM2 (50/125)orangeblack
OM3 (50/125, laser-optimized)aquaaqua
OM4 (50/125, laser-optimized)aqua, in Europe often Erika violetaqua or violet
OM5 (50/125, wideband)lime greenlime green

Two caveats. Connector colors are a convention, and manufacturers regularly deviate from it (more on that below). And outdoor cables are usually black, for UV protection, so there the color tells you nothing about the fiber type.

Yellow: single-mode

Yellow means single-mode: the fiber for LR, ER and beyond. Our OS2 LC/UPC patch cord is yellow with blue connectors, exactly by the book.

Watch the connector. Blue is UPC, with a flat-polished end face. Green is APC, angle-polished. Never mate the two: they don't make proper contact, you lose light and you can damage both connectors. If you need to go from one to the other, use a hybrid patch cord.

Orange, aqua, violet and lime green: multimode

Orange is the older generation of multimode: OM1 (62.5/125) and OM2 (50/125). Only OM3 and up are laser-optimized. If you find orange, always read the print: 62.5 and 50 µm look the same from the outside.

Aqua is OM3 and, per TIA-598, OM4 as well. That's exactly the problem: you can't tell from an aqua cable whether it's OM3 or OM4. That's why Erika violet became common for OM4 in Europe, and North America is now following. Our OM4 patch cord is violet, our OM3 patch cord aqua.

Lime green is OM5, the wideband variant. You rarely see it in practice.

Why you still read the print

Colors are a hint, not a guarantee. TIA-598 itself allows other colors, as long as the print on the jacket states the fiber type. And manufacturers deviate, connectors included.

An example from our own range: our OM3 patch cord has an aqua jacket but light beige connectors, while the convention says aqua. Nothing wrong with it, but if you only look at the connector, you'd think OM1. The print on the jacket tells you.

So:

  • Read the print — fiber type and core (for example OM4 50/125) are printed on the jacket.
  • Look at the connector — blue or green on single-mode tells you UPC or APC.
  • Don't mix fiber types in one link — joining multimode to single-mode costs around 17 to 20 dB according to the FOA. You'll see it as low or no Rx power.
  • Check the patch panel too — adapters often match the connector color. A violet adapter in a panel full of aqua is a useful hint that OM4 sits behind it, provided someone was consistent.
  • Label both ends — a label with the fiber type saves the next engineer the guesswork.

Colors inside a cable

When a cable holds more than one fiber, TIA-598 uses a fixed order for fibers 1 to 12: blue, orange, green, brown, slate, white, red, black, yellow, violet, rose and aqua. You'll meet that order in trunks and when terminating.

What to do now

Go through your patch cord stock and pull out OM1/OM2 if your equipment expects OM3 or OM4. Keep fiber types separate, in the cabinet and in your patch plan: that prevents most mistakes at 4 pm. When in doubt, order by fiber type: OS2, OM3 or OM4, or browse all cables. We deliver same day in Amsterdam.

Yvan Watchman

About the author

Yvan Watchman

Founder of FiberNxt and Xyphen IT

Yvan Watchman is the founder of FiberNxt and Xyphen IT. He has been building and running networks and data centre infrastructure in and around Amsterdam for years.

LinkedIn profile

Related products and services

Frequently asked questions

What color is a single-mode patch cable?

Yellow. TIA-598 specifies yellow for OS1, OS1a and OS2. Connectors are blue for UPC and green for APC. An outdoor cable may be black; in that case, read the print on the jacket.

Is a violet patch cable OM4?

Usually, yes. TIA-598 lists aqua for both OM3 and OM4, but in Europe especially, OM4 is often made in Erika violet precisely to tell it apart from OM3. Only the print on the jacket gives certainty.

Can I plug a green APC connector into a blue UPC port?

No. An APC connector has an angled end face, a UPC connector a flat one. They don't make proper contact, you lose light and you can damage both end faces. Use a hybrid patch cord if you need to go from one to the other.

Further reading